| Weight | 228 kg |
|---|
N25 ESFR: Storage Sprinkler – Pendent (BSPT International Only)
RM228.00
Reliable Storage Sprinkler Systems are designed to protect the storage of raw materials and components, commodities, or finished goods according to defined commodity classes and the configuration of the storage facility.
- Designed to be shorter, and more compact than other ESFR sprinklers, which allows piping to be installed further from the ceiling and obstructions
- Less susceptible to damage due to the smaller deflector and frame design
- Utilizes a levered fusible alloy solder link in either a 165°F (74°C) or a 212°F (100°C) rating
| Style | ESFR Pendent |
| K-Factor | 25.2 (362) |
| Temperature | 165°F (74°C), 212°F (100°C) |
| Thread Size | 1″ NPT(R1) |
| Finish | Bronze |
Related products
F1FR 56: Quick Response Sprinkler (1/2″ Orifice) Chrome
RM53.00 – RM86.00Price range: RM53.00 through RM86.00
Reliable Quick Response Sprinklers are ideal for protecting light and ordinary hazard applications such as office buildings, hotels, schools, and restaurants to control the spread of fire.
RELIABLE - Product Brochure
- Combines the durability of a standard sprinkler with the attractive low profile of a decorative sprinkler
- 3 mm glass bulb
- F1FR Series
| Style | Conventional, Pendent, Upright, Horizontal Sidewall (HSW) |
| K-Factor | 2.8(40), 4.2(60), 5.6(80) |
| Temperature | 135°F (57°C), 155°F (68°C), 175°F (79°C), 200°F (93°C), 286°F (141°C) |
| Thread Size | 1/2" NPT(R1/2) |
| Escutcheon | F1, F2, FP Push-on/Thread-off, FT |
| Cover Plate | CCP |
| Finish | Brass, Chrome, White Poly Coated, Custom |
F156: Standard Response Sprinkler (1/2″ Orifice) Chrome
RM29.00 – RM63.00Price range: RM29.00 through RM63.00
Reliable Standard Response Sprinklers are ideal for protecting ordinary and extra hazard applications such as parking garages, restaurant service areas, manufacturing facilities, and mills to control the spread of fire. Standard response sprinkler systems are designed to suppress and limit the spread of fire by wetting the area surrounding a flame to remove a fire’s fuel source.
RELIABLE - Product Brochure
- Combines the durability of a standard sprinkler with the attractive low profile of a decorative sprinkler
- 5 mm glass bulb
- F1 Series
| Style | Conventional, Pendent, Upright, Horizontal Sidewall (HSW) |
| K-Factor | 2.8(40), 4.2(60), 5.6(80) |
| Temperature | 135°F (57°C), 155°F (68°C), 175°F (79°C), 200°F (93°C), 286°F (141°C), 360°F (182°C) |
| Thread Size | 1/2" NPT(R1/2) |
| Escutcheon | F1, F2, FP Push-on/Thread-off, FT |
| Finish | Brass, Chrome, White Poly Coated, Custom |
F1-56SS: Stainless Steel Sprinkler – Pendent (1/2″ Orifice)
RM982.00
Reliable Quick Response Sprinklers are ideal for protecting light and ordinary hazard applications such as office buildings, hotels, schools, and restaurants to control the spread of fire.
RELIABLE - Product Brochure
- Combines the durability of a standard sprinkler with the attractive low profile of a decorative sprinkler
- 3 mm glass bulb
- F1 Series
| Style | Pendent, Recessed Pendent, Upright |
| K-Factor | 5.6(80), 8.0(115) |
| Temperature | 135°F (57°C), 155°F (68°C), 175°F (79°C), 200°F (93°C), 286°F (141°C) |
| Thread Size | 1/2" NPT(R1/2) |
| Escutcheon | F1, F2, FP Push-on/Thread-off, FT |
| Cover Plate | CCP |
| Finish | Stainless Steel |
F1 LO: Standard Response Sprinkler (17/32″ Orifice) Chrome
RM64.00 – RM67.00Price range: RM64.00 through RM67.00
Reliable Standard Response Sprinklers are ideal for protecting ordinary and extra hazard applications such as parking garages, restaurant service areas, manufacturing facilities, and mills to control the spread of fire. Standard response sprinkler systems are designed to suppress and limit the spread of fire by wetting the area surrounding a flame to remove a fire’s fuel source.
RELIABLE - Product Brochure
- All hazards for pendent and recessed pendent; Light Hazard only for EC Pendent and Recessed EC Pendent
- Available in standard coverage and extended coverage
- Extended coverage area up to 20"x20" (6.0m*6.0m) for EC pendent & recessed EC pendent
- 5mm glass bulb
- F1 Series
| Style | Conventional, Pendent, Upright |
| K-Factor | 8.0 (115) |
| Temperature | 135°F (57°C), 155°F (68°C), 175°F (79°C), 200°F (93°C), 286°F (141°C), 360°F (182°C) |
| Thread Size | 3/4" NPT(20mm) |
| Escutcheon | F1, FP for F1 Recessed |
| Finish | Brass, Chrome, White Poly Coated, Custom |
J112: Extended Coverage Sprinkler, Chrome (3/4″ NPT)
RM135.00
Reliable Extended Coverage Sprinklers are designed to protect larger areas than specified by installation rules for standard spray sprinklers.
RELIABLE - Product Brochure
- Extended Coverage for both Light and Ordinary Hazard occupancies for coverage areas from 144 ~ 400sqft
- Pendent, Recessed Pendent: Quick Response for Light Hazard - 16"x16" to 20"x20" sprinkler spacing
- Pendent, Recessed Pendent: Quick Response for Ordinary Hazard - 12"x12" & 14"x14" sprinkler spacing
- Standard Response for Ordinary Hazard - 16"x16" to 20"x20" sprinkler spacing
- 3mm glass bulb (J112)
| Style | Pendent, Recessed Pendent, Upright |
| K-Factor | 11.2 (160) |
| Temperature | Pendent: 155°F (68°C) Recessed Pendent: 200°F (93°C) Upright: 200°F (93°C) |
| Thread Size | 3/4" NPT(R3/4) |
| Escutcheon | Pendent, Recessed Pendent: F1, F2, FP Push-on/Thread-off |
| Finish | Bronze, Chrome, White Polyester |
JL-17 ESFR: Storage Sprinkler – Pendent (3/4″ NPT)
RM149.00
Reliable Storage Sprinkler Systems are designed to protect the storage of raw materials and components, commodities, or finished goods according to defined commodity classes and the configuration of the storage facility.
RELIABLE - Product Brochure
- Early suppression, fast response sprinkler for the protection of high-piled storage
- Levered fusible alloy solder link available with a 165°F (74°C) or a 212°F (100°C) temperature rating
- Delivers approximately 121gpm (458L/min) of water at 52psi (3.6bar)
| Style | ESFR Pendent |
| K-Factor | 16.8 (242) |
| Temperature | 165°F (74°C), 212°F (100°C) |
| Thread Size | 3/4" NPT(R3/4) |
| Finish | Bronze |
Ø83mm Water Shield – Threaded (FM Approved)
RM14.00
These are threaded water shields designed to create a pendent intermediate level sprinkler when installed on an approved sprinkler. (3-1/4" [83mm] diameter) water shields are threaded onto 1/2" sprinkler inlet threads prior to installation.
- Model E1 or E2
- 83mm Diameter Water Shield
- Screw on type: Available in 1/2"(15mm) & 3/4"(20mm) Sprinkler to be used without a guard
- FM approved
Wrench Flat Concealed for RFC30/43/49 & G5
RM863.00
Different wrench models are available for our sprinklers and valves. Please refer to the individual Technical Bulletin for the correct wrench.
RELIABLE - Product Brochure
| Model D | Model F3 | Model FC |
| Model GFR2 | Model G4 | Model H |
| Model H1 | Model J1 | Model N |
| Model RC1 | Model RJ | Model XLO2 |
| Model XLO EC | Model ZX Pendent | Model ZX HSW |